L24 / Transmission-line parameters
Transmission-Line Parameters III
Use physical radius to find capacitance, split a nominal π shunt and check phase current against three-phase reactive supply.
01 / UNDERSTAND & PREDICT
Understand the model, then predict the result
- Use physical radius rather than magnetic GMR in electrostatic calculations.
- Relate C, B, phase current and total three-phase reactive power.
- Interpret the two shunt branches and reactive power sign.
Potential outside a conducting cylinder
An ideal conductor has zero electric field inside its metal. Integrating the outside field uses the physical surface radius r; the internal magnetic-linkage correction does not apply to electric potential.
Phase-to-neutral capacitance
Balanced charges sum to zero. For equal spacing or a fully transposed arrangement, the mutual-distance terms reduce to GMD. The neutral is an electrical reference, not an added physical conductor.
From a rate to a route shunt
Ctotal=C′ℓ and Btotal=ωCtotal. Unit conversions matter: nF/km multiplied by km gives nF, then divide by 1000 for μF. B is positive capacitive susceptance in Y=jB.
Current and three-phase reactive supply
The phase charging current leads phase voltage by 90°. Under the uniform-voltage estimate, QC is positive capacitive supply; the absorbed complex reactive power is −QC. The line-voltage formula already includes all three phases.
Nominal π and local terminal voltage
Each π end has jBtotal/2. Its current uses the local phase voltage. With equal terminal magnitudes, each end supplies half QC; otherwise compute each end separately. IR=0 means no receiving load, not zero sending charging current.
Baseline example: check each step
- Dm=(4×6×10)⅓=6.214465 m. ln(Dm/r)=6.09557759, using r=0.014 m.
- C′n=9.126699 nF/km; Ctotal=9.126699×120.7008/1000=1.1015999 μF.
- B′=3.4406845 μS/km; Btotal=0.41529337 mS. Each π-end shunt is 0.20764669 mS.
- Vphase=138/√3=79.67434 kV; |Ich|=33.08822 A. QC=0.41529337×138²/1000=7.908847 Mvar; absorbed Q=−7.908847 Mvar.
- Using magnetic GMR as r underestimates C′ by 3.944%. At 0.95 times voltage, QC becomes 0.95² times its original value, while C and B stay unchanged.
Cross-check the original slides
02 / EXPLORE
Change one input and explain the response
Reduce line voltage by 5% and predict QC before changing the slider. Then double length in Python: C, B, I and QC should double, while C′ stays fixed.
Advanced parameters / test readings
Preparing the model.
Charging reactive supply versus voltage
Capacitance versus physical radius
Current intermediate values and numerical checks
Balanced, equal-spacing or fully transposed overhead line in a uniform dielectric; earth and shield wires omitted. Charging uses uniform line voltage and does not solve sending/receiving voltage rise. The π diagram shows parameter placement; R and X are symbolic in this capacitance-only experiment.
03 / EDIT & COMPUTE
Edit code to reproduce the model independently
Reproduce the baseline, then modify the parameter scan. The source contains reusable independent model functions; edit the current function and inspect numerical checks.
case is a snapshot of the controls when you press Run. Call solve(case) and assign the final solution to result to plot it.
The first run needs internet access to download Python. Computation stays in your browser; the solver uses only the standard library.
Ready to run.
Output appears here.
Last Python run and current control reference
Inspect and edit the model source (advanced)
Edit this module's function and run again. case.module selects the module; solve(case) returns values, plots, and checks. The parameter experiment keeps the original JavaScript reference for comparison.
04 / CHECK & EXPLAIN
Companion experiment practice and feedback
L24 example: distances 4, 6 and 10 m; physical radius 14 mm; air ε=ε0=8.8541878×10⁻¹² F/m; f=60 Hz; length 75 mi=120.7008 km; VLL=138 kV. GMR=10.90 mm is supplied only for a deliberate comparison.
Practice uses fixed baseline inputs independently of the controls. Each field displays its tolerance.
See the worked solution
- Dm=(4×6×10)⅓=6.214465 m. ln(Dm/r)=6.09557759, using r=0.014 m.
- C′n=9.126699 nF/km; Ctotal=9.126699×120.7008/1000=1.1015999 μF.
- B′=3.4406845 μS/km; Btotal=0.41529337 mS. Each π-end shunt is 0.20764669 mS.
- Vphase=138/√3=79.67434 kV; |Ich|=33.08822 A. QC=0.41529337×138²/1000=7.908847 Mvar; absorbed Q=−7.908847 Mvar.
- Using magnetic GMR as r underestimates C′ by 3.944%. At 0.95 times voltage, QC becomes 0.95² times its original value, while C and B stay unchanged.
Finally, explain in your own words
- What are the inputs, references, and main assumptions?
- Reduce line voltage by 5% and predict QC before changing the slider. Then double length in Python: C, B, I and QC should double, while C′ stays fixed.
- Did your code edit change physical parameters, the method, or representation bases? Which check helps identify that?
Passing numerical and understanding checks records this lecture’s companion practice as “practice checks passed.”