L18 / Three-phase transformers

Three-Phase Transformers II

Derive a balanced Y–Δ branch from actual terminal quantities and system bases; distinguish bank, autotransformer and tap ratios.

Available36 slides
From actual quantities to the per-unit transformer branch

01 / UNDERSTAND & PREDICT

Understand the model, then predict the result

Finalized lecture slides

Open / download original PDF ↗

Follow the original explanations, diagrams, derivations, and examples in slide order, then use the companion experiment below.

L18 original slide 1 of 36
L18 · 1 / 36
Slide text
Loading slide text.

Figures and page order follow the student PDF for this lecture.

The L18 bank is rated 60 MVA, 138/13.8 kV, Y–Δ. Its terminal ratio is 10, but its winding ratio is 10/√3. On a 100 MVA system base, does changing base change its physical impedance?
  • Convert winding impedance into an equivalent Y phase model.
  • Check per-unit base changes by recovering physical ohms.
  • Distinguish a physical tap, fixed voltage bases and directional complex ratios.
Three-phase transformer network and taps: baseline circuit or quantitative model illustration
Model illustration at baseline inputs. Change the parameters in the next section to explore the live diagram.

Actual series impedances and terminal-phase model

Z_{Y,H}=Z_H+a^2Z_L,\quad Z_{Y,L}=\frac{Z_L+Z_H/a^2}{3},\quad Z_{Y,H}=3a^2Z_{Y,L}

Retain both winding resistances and leakage reactances; neglect excitation for the loaded approximation. Refer both winding series effects to H or L, then replace the physical L delta impedance with its equivalent Y value. The transformer remains Y–Δ; the equivalent L neutral is a voltage reference, not a grounding connection.

Define the bases before normalizing

V_{B,\phi}=V_{B,LL}/\sqrt3,\quad I_B=\frac{S_B}{\sqrt3V_{B,LL}},\quad Z_B=\frac{V_{B,LL}^2}{S_B}

Choose one total three-phase power base and the H line-voltage base. The rated Y–Δ terminal ratio gives VB,L=VB,H/(√3a). Derive both terminal-phase voltage bases, line-current bases and phase-impedance bases from these choices. Bases are positive real magnitudes and contain no connection angle.

Compatible bases cancel the magnitude ratio

\frac{V_{B,\phi,H}}{V_{B,\phi,L}}=\frac{I_{B,L}}{I_{B,H}}=\sqrt3a,\quad v_H=e^{-j\delta_{LH}}v_L,\quad i_L=e^{j\delta_{LH}}i_H

Across the nominal ideal element, divide actual RMS voltages by terminal-phase bases and line currents by line-current bases. The same real √3a factor occurs in each actual ratio and base ratio, so it cancels. The connection displacement δLH=−30° remains. With loading, retain the H series drop before transferring the voltage.

Assemble the nominal per-unit branch

v_H=z_{eq}i_H+e^{-j\delta_{LH}}v_L,\quad i_L=e^{j\delta_{LH}}i_H,\quad s_H-s_L=z_{eq}|i_H|^2

Compatible voltage bases give the same combined per-unit series impedance on either side. Normalizing total three-phase power by the common SB removes the factor 3: s=vi*. H current enters and L current leaves. The ideal element conserves complex power; the full branch input minus output equals its series complex-power loss.

Autotransformer power paths

S_{magnetic}/S_{terminal}=(V_H-V_L)/V_H

The source slides show a series-aiding step-down autotransformer: VH=(Ns+Nc)e per turn and VL=Nc e per turn. Power is transferred through both a direct electrical path and magnetic coupling. The common connection removes galvanic isolation; a conventional two-winding bank model cannot represent that isolation difference.

Tap extension with fixed bases

v_H=z_{eq}i_H+t_{HL}v_L,\quad i_L=t_{HL}^*i_H,\quad t_{HL}=\tau e^{j\theta_{HL}}

Slides 33–35 introduce physical taps and the off-nominal magnitude τ. This web experiment extends the nominal branch of slide 17 to τ≠1. For Y–Δ abc, δLH=−30° and θHL=+30°. Keep voltage bases fixed, set tHL=τexp(jθHL), and use iL=tHL* iH. Increasing active H turns raises τ and reduces ideal LV voltage at fixed HV voltage.

Baseline example: check each step

  1. a=(138/√3)/13.8=5.77350; rated terminal ratio is 10. On compatible rated voltage bases, ideal magnitude ratio in pu is one.
  2. z100=(0.006+j0.090)×100/60=0.010+j0.150 pu. ZB,H=138²/100=190.44 Ω.
  3. Recover ZY,H=1.9044+j28.566 Ω. On L, ZY,L=0.019044+j0.28566 Ω and ZΔ,L=0.057132+j0.85698 Ω.
  4. At no load and τ=1, vL=1∠−30° pu, corresponding to 13.8∠−30° kV line voltage with VAB,H at 0°. At τ=1.05, |VLL,L|=13.8/1.05=13.14286 kV.
  5. With loading, solve vL=(vH−z iH)/tHL and iL=tHL* iH. Input minus output complex power equals z|iH|²; inspect both balance checks.
Original slide headings for this lecture36
  1. 1Three-Phase Transformers II
  2. 2Lecture outline
  3. 3PART 1 From single-phase to three-phase model
  4. 4Quick recap: single-phase transformer
  5. 5Quick recap: reduced series model
  6. 6Three-phase Y–Δ connection
  7. 7Series impedance on H or L
  8. 8L-side Δ→Y equivalent
  9. 9Phase voltages and displacement
  10. 10Actual terminal-phase voltages
  11. 11Actual terminal currents
  12. 12Actual impedance and branch equation
  13. 13Define all system bases
  14. 14Relations between H and L bases
  15. 15Normalize voltage and current
  16. 16Normalize impedance and power
  17. 17Assemble the balanced Y–Δ branch
  18. 18PART 2 Bank example and checks
  19. 19Bank example: data
  20. 20Bank example: solution route
  21. 21Bank example: voltage ratios
  22. 22Bank example: no-load phasor
  23. 23Bank example: change of base
  24. 24Bank example: recover ohms
  25. 25Bank example: rated currents
  26. 26PART 3 Autotransformer concept
  27. 27Two-winding and autotransformer
  28. 28Series and common sections
  29. 29Autotransformer power paths
  30. 30Autotransformer applications
  31. 31Three-phase autotransformer
  32. 32PART 4 Tap ratio concept
  33. 33Tapped winding construction
  34. 34Three different ratios
  35. 35Tap-changing equipment
  36. 36Summary
Cross-check the original slides

02 / EXPLORE

Change one input and explain the response

Set input-current loading to 1 and vary τ. Explain voltage drop and check power balance. Then change only Sbase: physical ohms, line voltages and currents should stay unchanged.

Advanced parameters / test readings

Preparing the model.

Active winding ratio—
System-base resistance—
System-base reactance—
LV terminal line voltage—
LV angle relative to HV—
Physical HV phase resistance—
Physical LV delta winding resistance—
Series real-power loss—

LV voltage versus H-side tap

LV voltage versus input-current loading

Current intermediate values and numerical checks

Balanced positive sequence, Y–Δ abc with δLH=−30°, fixed rated voltage bases and H-side series impedance; excitation neglected. HV voltage is fixed at 1 pu. Loading prescribes HV input-current magnitude and lagging power factor, not a constant-power LV load. Tap changes active H turns. Autotransformer construction is covered in slides and concepts, outside this two-winding numerical branch.

03 / EDIT & COMPUTE

Edit code to reproduce the model independently

Reproduce the baseline, then modify the parameter scan. The source contains reusable independent model functions; edit the current function and inspect numerical checks.

case is a snapshot of the controls when you press Run. Call solve(case) and assign the final solution to result to plot it.

Download teaching models

The first run needs internet access to download Python. Computation stays in your browser; the solver uses only the standard library.

Ready to run.

Output appears here.
Inspect and edit the model source (advanced)

Edit this module's function and run again. case.module selects the module; solve(case) returns values, plots, and checks. The parameter experiment keeps the original JavaScript reference for comparison.

04 / CHECK & EXPLAIN

Companion experiment practice and feedback

Fixed practice inputs

L18 example: 60 MVA, 138/13.8 kV, Y–Δ abc; equipment z=0.006+j0.090 pu. System base is 100 MVA with rated line-voltage bases. τ=1, no load.

Practice uses fixed baseline inputs independently of the controls. Each field displays its tolerance.

±0.001
±0.001 pu
±0.0001 Ω

At no load with fixed voltage bases and HV voltage, what does τ=1.05 do?

Finally, explain in your own words

  1. What are the inputs, references, and main assumptions?
  2. Set input-current loading to 1 and vary τ. Explain voltage drop and check power balance. Then change only Sbase: physical ohms, line voltages and currents should stay unchanged.
  3. Did your code edit change physical parameters, the method, or representation bases? Which check helps identify that?

Passing numerical and understanding checks records this lecture’s companion practice as “practice checks passed.”

ECE 685 · L18

Course learning assistant

Ask about course material, request an explanation, or follow up.

Choose a context, then ask “What does this mean?”