L18 / Three-phase transformers
Three-Phase Transformers II
Derive a balanced Y–Δ branch from actual terminal quantities and system bases; distinguish bank, autotransformer and tap ratios.
01 / UNDERSTAND & PREDICT
Understand the model, then predict the result
- Convert winding impedance into an equivalent Y phase model.
- Check per-unit base changes by recovering physical ohms.
- Distinguish a physical tap, fixed voltage bases and directional complex ratios.
Actual series impedances and terminal-phase model
Retain both winding resistances and leakage reactances; neglect excitation for the loaded approximation. Refer both winding series effects to H or L, then replace the physical L delta impedance with its equivalent Y value. The transformer remains Y–Δ; the equivalent L neutral is a voltage reference, not a grounding connection.
Define the bases before normalizing
Choose one total three-phase power base and the H line-voltage base. The rated Y–Δ terminal ratio gives VB,L=VB,H/(√3a). Derive both terminal-phase voltage bases, line-current bases and phase-impedance bases from these choices. Bases are positive real magnitudes and contain no connection angle.
Compatible bases cancel the magnitude ratio
Across the nominal ideal element, divide actual RMS voltages by terminal-phase bases and line currents by line-current bases. The same real √3a factor occurs in each actual ratio and base ratio, so it cancels. The connection displacement δLH=−30° remains. With loading, retain the H series drop before transferring the voltage.
Assemble the nominal per-unit branch
Compatible voltage bases give the same combined per-unit series impedance on either side. Normalizing total three-phase power by the common SB removes the factor 3: s=vi*. H current enters and L current leaves. The ideal element conserves complex power; the full branch input minus output equals its series complex-power loss.
Autotransformer power paths
The source slides show a series-aiding step-down autotransformer: VH=(Ns+Nc)e per turn and VL=Nc e per turn. Power is transferred through both a direct electrical path and magnetic coupling. The common connection removes galvanic isolation; a conventional two-winding bank model cannot represent that isolation difference.
Tap extension with fixed bases
Slides 33–35 introduce physical taps and the off-nominal magnitude τ. This web experiment extends the nominal branch of slide 17 to τ≠1. For Y–Δ abc, δLH=−30° and θHL=+30°. Keep voltage bases fixed, set tHL=τexp(jθHL), and use iL=tHL* iH. Increasing active H turns raises τ and reduces ideal LV voltage at fixed HV voltage.
Baseline example: check each step
- a=(138/√3)/13.8=5.77350; rated terminal ratio is 10. On compatible rated voltage bases, ideal magnitude ratio in pu is one.
- z100=(0.006+j0.090)×100/60=0.010+j0.150 pu. ZB,H=138²/100=190.44 Ω.
- Recover ZY,H=1.9044+j28.566 Ω. On L, ZY,L=0.019044+j0.28566 Ω and ZΔ,L=0.057132+j0.85698 Ω.
- At no load and τ=1, vL=1∠−30° pu, corresponding to 13.8∠−30° kV line voltage with VAB,H at 0°. At τ=1.05, |VLL,L|=13.8/1.05=13.14286 kV.
- With loading, solve vL=(vH−z iH)/tHL and iL=tHL* iH. Input minus output complex power equals z|iH|²; inspect both balance checks.
Cross-check the original slides
02 / EXPLORE
Change one input and explain the response
Set input-current loading to 1 and vary τ. Explain voltage drop and check power balance. Then change only Sbase: physical ohms, line voltages and currents should stay unchanged.
Advanced parameters / test readings
Preparing the model.
LV voltage versus H-side tap
LV voltage versus input-current loading
Current intermediate values and numerical checks
Balanced positive sequence, Y–Δ abc with δLH=−30°, fixed rated voltage bases and H-side series impedance; excitation neglected. HV voltage is fixed at 1 pu. Loading prescribes HV input-current magnitude and lagging power factor, not a constant-power LV load. Tap changes active H turns. Autotransformer construction is covered in slides and concepts, outside this two-winding numerical branch.
03 / EDIT & COMPUTE
Edit code to reproduce the model independently
Reproduce the baseline, then modify the parameter scan. The source contains reusable independent model functions; edit the current function and inspect numerical checks.
case is a snapshot of the controls when you press Run. Call solve(case) and assign the final solution to result to plot it.
The first run needs internet access to download Python. Computation stays in your browser; the solver uses only the standard library.
Ready to run.
Output appears here.
Last Python run and current control reference
Inspect and edit the model source (advanced)
Edit this module's function and run again. case.module selects the module; solve(case) returns values, plots, and checks. The parameter experiment keeps the original JavaScript reference for comparison.
04 / CHECK & EXPLAIN
Companion experiment practice and feedback
L18 example: 60 MVA, 138/13.8 kV, Y–Δ abc; equipment z=0.006+j0.090 pu. System base is 100 MVA with rated line-voltage bases. τ=1, no load.
Practice uses fixed baseline inputs independently of the controls. Each field displays its tolerance.
See the worked solution
- a=(138/√3)/13.8=5.77350; rated terminal ratio is 10. On compatible rated voltage bases, ideal magnitude ratio in pu is one.
- z100=(0.006+j0.090)×100/60=0.010+j0.150 pu. ZB,H=138²/100=190.44 Ω.
- Recover ZY,H=1.9044+j28.566 Ω. On L, ZY,L=0.019044+j0.28566 Ω and ZΔ,L=0.057132+j0.85698 Ω.
- At no load and τ=1, vL=1∠−30° pu, corresponding to 13.8∠−30° kV line voltage with VAB,H at 0°. At τ=1.05, |VLL,L|=13.8/1.05=13.14286 kV.
- With loading, solve vL=(vH−z iH)/tHL and iL=tHL* iH. Input minus output complex power equals z|iH|²; inspect both balance checks.
Finally, explain in your own words
- What are the inputs, references, and main assumptions?
- Set input-current loading to 1 and vary τ. Explain voltage drop and check power balance. Then change only Sbase: physical ohms, line voltages and currents should stay unchanged.
- Did your code edit change physical parameters, the method, or representation bases? Which check helps identify that?
Passing numerical and understanding checks records this lecture’s companion practice as “practice checks passed.”